Type SHD Flat Portable Power Cable 2kV

Standard:ICEA S-75-381
Material: Cu/EPR/TWCB/CPE
Application: Type SHD Cables are designed for use as heavy duty trailing cable on mining equipment where maximum safety is required. Also suitable for high voltage distribution in underground mines where portable power is required.

Type SHD Flat Portable Power Cable 2kV

Type SHD Flat Portable Power Cable 2kV Application

Type SHD Flat Portable feeder cable is Heavy duty portable power cable for use in circuits not exceeding 2,000 volts. It is specially designed for use on continuous miners requiring grounding conductors and metallic shielding over each conductor. Recommended maximum continuous conductor temperature is 90°C.

This Type SHD portable mining cable has excellent impact and abrasion resistance, and withstand exposure to oil, acids, alkalies, heat, moisture and most chemicals, Indent printed for easy identification Rope lay stranding for maximum flex life, cable core bound for superior flexibility and toughness.

Type SHD Flat Portable Power Cable 2kV Standard

ICEA S-75-381/NEMA WC 58

ASTM B 172

ASTM B 33

CAN/CSA-C22.2 No.96

Type SHD Flat Portable Power Cable 2kV Construction

Conductors  Stranded annealed tinned copper conductor.
Insulation EPR.
Insulation Shield Tinned copper/textile braid.
Grounding Conductor Tinned copper conductor with semi-conductive thermoset compound.
Sheath  Reinforced extra-heavy-duty Chlorinated Polyethylene(CPE), black.
Other sheath materials can be offered as an option.
Options: Other jacket materials such as CSP/PCP/NBR/PVC are available upon request.
Two-layer jacket with reinforcing fibre between the two layers can be offered
as an option

Type SHD Flat Portable Power Cable 2kV Specification

Construction Grounding
Conductor Size
Nominal
Insulation
Thickness
Nominal
Overall Diameter
Height×Width
Nominal
Weight
Ampacity
No. of cores×
AWG/kcmil
AWG/kcmil mm mm kg/km A
3×2 6 1.8 23.9×62.2 3338 159
3×1 5 2 26.4×67.1 3780 184
3×1/0 4 2 27.4×71.6 4338 211
3×2/0 3 2 30.0×76.0 4980 243
3×3/0 2 2 31.8×83.6 5789 279

Ampacity-Based on a conductor temperature of 90℃ and an ambient air temperature of 40℃, per ICEA S-75-381.

Please note that the above specifications are “general specifications” that pertain to the majority of our production. These specifications should only be used for general, informational purposes. All dimensions and specifications are nominal and are subject to normal manufacturing tolerances. All specifications are subject to change without prior notice. All pictures shown are for illustration purposes only. Actual product may vary.