P6/P13 BFOU Fire Resistant Mud Resistant Cable 3.6/6kv
P6/P13 BFOU Fire Resistant Mud Resistant Cable 3.6/6kv Application
P6/P13 BFOU 3.6/6Kv Cable is fire resistant, flame retardant, low smoke, halogen free and mud resistant, used for fixed installation for medium voltage power with the rated voltage of 3.6/6Kv.
These P6/P13 BFOU 3.6/6Kv cables can be installed on drilling ships, drilling platforms ( jack up, semi-submersible), Production Platforms ( TLP, semi-submersible, SPAR, fixed platforms) and FPSO/FSO.
P6/P13 BFOU Fire Resistant Mud Resistant Cable 3.6/6kv Standards
Design | IEC60092-354 |
Conductor | IEC60228 |
Insulation | IEC60092-351 |
sheathed | IEC60092-359 |
Flame Retardant | IEC 60332-1,IEC60332-3-22 |
Fire Resistant | IEC 60331 |
Smoke Density | IEC61034 |
Mud Resistant | NEK TS 606:2009 |
P6/P13 BFOU Fire Resistant Mud Resistant Cable 3.6/6kv Construction
Classification | Code | Construction details |
Conductor | Tinned Annealed Stranded Copper Wire | |
Conductor Screen | Semiconducting material | |
Insulation | B | Mica Tape+EP Rubber/XLPE |
Insulation Screen | Semiconducting material and tinned copper wire braid | |
Filler | Water blocking fillers, if required | |
Bedding | Halogen free compound, PETP wrapping tape will be applied over the bedding, if required | |
Inner Sheath | F | Halogen free thermosetting compound |
Armor | O | Tinned Copper wire braided |
Outer Sheath | U | Mud Resistant, Halogen-free Thermosetting compound SHF Mud |
P6/P13 3.6/6kV BFOU Fire Resistant Mud Resistant Cable Characteristics
Nominal Cross Section Area | mm² | 25 | 35 | 50 | 70 | 95 | 120 | 150 |
Nominal Conductor Diameter | mm | 6.5 | 7.4 | 8.7 | 10.3 | 12.2 | 13.8 | 15.1 |
Maximum DC Resistant@20℃ | Ω/km | 0.734 | 0.529 | 0.391 | 0.27 | 0.195 | 0.154 | 0.126 |
Continuous Current Rating@45℃1 Core | A | 127 | 157 | 196 | 242 | 293 | 339 | 389 |
Continuous Current Rating@45℃3 Core | A | 89 | 110 | 137 | 169 | 205 | 237 | 272 |
Short Circuit Current 1s | A | 3580 | 5010 | 7150 | 10020 | 13590 | 17170 | 21460 |
Operating Voltage | KV | 3.6/6 | 3.6/6 | 3.6/6 | 3.6/6 | 3.6/6 | 3.6/6 | 3.6/6 |
Nominal Cross Section Area | mm² | 185 | 240 | 300 | 400 | 500 | 630 |
Nominal Conductor Diameter | mm | 17.0 | 19.6 | 21.9 | 24.5 | 27.5 | 32.3 |
Maximum DC Resistant@20℃ | Ω/km | 0.1 | 0.0762 | 0.0607 | 0.0475 | 0.0369 | 0.0286 |
Continuous Current Rating@45℃1 Core | A | 444 | 522 | 601 | 690 | 780 | 890 |
Continuous Current Rating@45℃3 Core | A | 311 | 365 | 421 | 483 | 546 | 623 |
Short Circuit Current 1s | A | 26470 | 34340 | 42930 | 57230 | 71540 | 90140 |
Operating Voltage | KV | 3.6/6 | 3.6/6 | 3.6/6 | 8.7/15 | 8.7/15 | 8.7/15 |
Note: For more than 4-cores, the current ratings may be calculated from the following formula (IN=I1/ ³√ N ), I1= Current rating for 1-core, N = Number of cores.
Ambient Temperature Correction Factors
Ambient Temperature Correction Factors | 35 | 40 | 45 | 50 | 55 | 60 | 65 | 70 | 75 | 80 |
Rating Factor | 1.1 | 1.05 | 1.0 | 0.94 | 0.88 | 0.82 | 0.74 | 0.67 | 0.58 | 0.47 |
P6/P13 BFOU Fire Resistant Mud Resistant Cable 3.6/6kv Specification
Construction No. of cores×Cross section |
Nominal Insulation Thickness |
Nominal Inner Sheath Thickness |
Nominal Outer Sheath Thickness |
Nominal Overall Diameter |
Nominal Weight |
(mm²) | mm | mm | mm | mm | kg/km |
1×16 | 2.5 | 1 | 1.6 | 24.8 | 950 |
1×25 | 2.5 | 1 | 1.6 | 26.3 | 1110 |
1×35 | 2.5 | 1 | 1.7 | 27.6 | 1260 |
1×50 | 2.5 | 1 | 1.7 | 29.1 | 1460 |
1×70 | 2.5 | 1 | 1.8 | 30.9 | 1740 |
1×95 | 2.5 | 1 | 1.9 | 33.2 | 2110 |
1×120 | 2.5 | 1 | 1.9 | 34.9 | 2430 |
1×150 | 2.5 | 1.2 | 2 | 36.9 | 2890 |
1×185 | 2.5 | 1.2 | 2.1 | 39.1 | 3370 |
1×240 | 2.6 | 1.2 | 2.2 | 42.2 | 4100 |
1×300 | 2.8 | 1.2 | 2.3 | 44.7 | 4810 |
1×400 | 3 | 1.4 | 2.5 | 48.1 | 5810 |
1×500 | 3.2 | 1.4 | 2.6 | 52.1 | 7030 |
1×630 | 3.2 | 1.4 | 2.8 | 56.5 | 8630 |
3×16 | 2.5 | 1.2 | 2.3 | 48.2 | 3550 |
3×25 | 2.5 | 1.2 | 2.4 | 51.5 | 4180 |
3×35 | 2.5 | 1.4 | 2.5 | 54.7 | 4820 |
3×50 | 2.5 | 1.4 | 2.6 | 57.4 | 5490 |
3×70 | 2.5 | 1.4 | 2.8 | 61.6 | 6590 |
3×95 | 2.5 | 1.6 | 2.9 | 66.2 | 7920 |
3×120 | 2.5 | 1.6 | 3.1 | 70.1 | 9150 |
3×150 | 2.5 | 1.6 | 3.2 | 74 | 10460 |
3×185 | 2.5 | 1.6 | 3.4 | 78.6 | 12010 |
3×240 | 2.6 | 1.8 | 3.6 | 86.3 | 14690 |
3×300 | 2.8 | 1.8 | 3.9 | 92.3 | 17130 |
Please note that the above specifications are “general specifications” that pertain to the majority of our production. These specifications should only be used for general, informational purposes. All dimensions and specifications are nominal and are subject to normal manufacturing tolerances. All specifications are subject to change without prior notice. All pictures shown are for illustration purposes only. Actual product may vary. Classification certification like CCS, DNV, BV, LR, NK, KR, RS shall be provided upon request.