Type 240 Mining Power Cable 1.1 to 11KV

Standard:AS/NZS 1802:2003
Application: mainly used extensively for feeder connection between a transformer and gate-end box or similar, or as continuous miner cable or feeder cables to pumps.

Type 240 Mining Power Cable 1.1 to 11KV

Type 240 Mining Power Cable 1.1 to 11KV Application

These type 240 cables are mainly used as feeder cables for power supply to machinery or longwall supply. This Cable used extensively for feeder connection between the transformer and gate-end box or similar, or as continuous miner cable or feeder cables to pumps.

Having three pilots, the cable can be used in long runs, without compromising pilot control protection system resistance limitations. This cable could also be suitable for use in underground coal mining applications.

Type 240 Mining Power Cable 1.1 to 11KV Standard

AS/NZS 1125,
AS/NZS 3808,
AS/NZS 1802,
AS/NZS 5000.1

Type 240 Mining Power Cable 1.1 to 11KV Construction

Type 240 Mining Power Cable 1.1 to 11KV Construction

Type 240 Mining Power Cable 1.1 to 11KV Construction

3×Conductors  Flexible stranded tinned annealed copper conductor.
Conductor Screen 1.1/1.1kV – polyester barrier tape, 3.3/3.3kV and above – polyester barrier tape and extruded semiconductive tape.
Insulation  EPR.
Insulation Screen  Semiconductive tape.
Composite Screen (earth conductor) Tinned annealed copper braiding interwove with polyester yarn.
Cradle Separator  Semiconductive PCP.
3×Interstitial Pilot EPR covered flexible stranded tinned copper conductor.
Sheath  Heavy duty PCP sheath.

Type 240 Mining Power Cable 1.1 to 11KV Technical Data

Voltage Rating   1.1, 3.3, 6.6, 11kV
Operating Conductor Temperature   -25 to 90°C
Emergency Conductor Temperature   130°C
Short Circuit Conductor Temperature   Max. 250°C for 5 sec
Max. Working Tension   0.02kN/mm² (total)

Type 240 Mining Power Cable 1.1 to 11KV Specification

Type 240.1

Nominal
Conductor Area
Insulation
Thickness
Core screen
Area of Screen
Pilot Conductor
Thickness of Covering
Thickness of
Sheath
Nominal
Overall
Diameter
Nominal
Weight
mm2 mm mm2 mm mm mm kg/100m
6 1.5 7.2 1 3.8 30 131
10 1.5 8.6 1 3.8 32.6 159
16 1.6 9.6 1 4 35.8 202
25 1.6 11.3 1.2 4.3 39.7 265
35 1.6 12.4 1.2 4.6 43.1 326
50 1.7 14.1 1.2 5 47.7 404
70 1.8 16.5 1.2 5.4 53.9 533
95 2 18.2 1.2 6 58.6 635
120 2.1 20.3 1.4 6.4 64.4 775
150 2.3 22.3 1.4 6.9 70.2 940
185 2.5 30.2 1.4 7.4 77.4 1150
240 2.8 33.6 1.6 8.2 86 1440
300 3 50.1 1.6 8.8 95.1 1810

Type 240.3

Nominal
Conductor Area
Insulation
Thickness
Core screen
Area of Screen
Pilot Conductor
Thickness of Covering
Thickness of
Sheath
Nominal
Overall
Diameter
Nominal
Weight
mm2 mm mm2 mm mm mm kg/100m
16 3 13.1 1.4 5.3 46.2 306
25 3 14.8 1.4 5.6 50.1 379
35 3 15.8 1.4 5.9 53.5 444
50 3 17.2 1.4 6.3 57.6 525
70 3 18.6 1.4 6.6 62.5 656
95 3 20.3 1.4 7.1 66.2 750
120 3 27.2 1.6 7.4 72 910
150 3 39.6 1.6 7.8 78 1115
185 3 42.2 1.8 8.2 83.4 1280
240 3 46.6 1.8 8.8 90.3 1540
300 3 63.2 1.8 9.4 98.4 1920

Type 240.6

Nominal
Conductor Area
Insulation
Thickness
Core screen
Area of Screen
Pilot Conductor
Thickness of Covering
Thickness of
Sheath
Nominal
Overall
Diameter
Nominal
Weight
mm2 mm mm2 mm mm mm kg/100m
16 5 17.2 1.4 6.4 57.3 440
25 5 18.6 1.4 6.7 61.2 521
35 5 18.6 1.6 7 64.6 593
50 5 21.3 1.6 7.3 68.5 685
70 5 23.4 1.6 7.7 73.7 830
95 5 29.2 1.6 8.1 77.8 954
120 5 31.7 1.8 8.5 83.1 1111
150 5 45.7 1.8 8.9 89.1 1335
185 5 48.4 1.8 9.3 94.5 1515
240 5 52.8 1.8 9.9 101.4 1810
300 5 71.5 1.8 10.4 109.3 2190

Type 240.11

Nominal
Conductor Area
Insulation
Thickness
Core screen
Area of Screen
Pilot Conductor
Thickness of Covering
Thickness of
Sheath
Nominal
Overall
Diameter
Nominal
Weight
mm2 mm mm2 mm mm mm kg/100m
25 7.6 23.7 2 8.1 75.6 752
35 7.6 30.2 2 8.4 79.7 860
50 7.6 31.7 2 8.7 83.6 961
70 7.6 34.1 2 9.1 88.8 1125
95 7.6 47.5 2 9.6 93.7 1300
120 7.6 51 2.2 9.9 98.8 1470
150 7.6 53.7 2.2 10.3 103.5 1659
185 7.6 57.2 2.2 10.7 108.8 1880

Please note that the above specifications are “general specifications” that pertain to the majority of our production. These specifications should only be used for general, informational purposes. All dimensions and specifications are nominal and are subject to normal manufacturing tolerances. All specifications are subject to change without prior notice. All pictures shown are for illustration purposes only. Actual product may vary.

Reviews

There are no reviews yet.

Be the first to review “Type 240 Mining Power Cable 1.1 to 11KV”

Your email address will not be published. Required fields are marked *

This site uses Akismet to reduce spam. Learn how your comment data is processed.