Type MP-GC Mine Power Feeder Cable 5Kv
Type MP-GC Mine Power Feeder Cable 5Kv Application
This Type MP-GC power feeder cable is designed for use in high voltage distribution circuits for permanent (or semi-portable) installations in bore holes, shafts, open pits, strip mines, and tunnels. It is used for connections between units of mine distribution systems, suitable for installing in the duct, conduit or open air. The cable can be used in wet or dry locations, installed in conduit or duct, (not to exceed maximum rated voltage), and suitable for direct burial applications.
Rated Voltage of 5Kv, 8kv, 15Kv, 25Kv is available upon request.
Type MP-GC Mine Power Feeder Cable 5KvStandard
ICEA S-75-381/NEMA WC 58
ASTM B 172
ASTM B 33
CAN/CSA-C22.2 No.96
Type MP-GC Mine Power Feeder Cable 5Kv Construction
Conductors | Stranded annealed bare copper conductor. |
Conductor Shield | Semi-conducting layer. |
Insulation | EPR. |
Insulation Shield | Semi-conducting layer + copper tape. |
Ground Check Conductor | Copper conductor with a yellow polypropylene insulation. |
Grounding Conductor | Tinned copper conductor. |
Sheath | Chlorinated Polyethylene(CPE), black. Other sheath materials can be offered as an option. |
Options: | Other jacket materials such as CSP/PCP/NBR/PVC are available upon request. Two-layer jacket with reinforcing fibre between the two layers can be offered as an option. |
Type MP-GC Mine Power Feeder Cable 5Kv Specification
Construction | Grounding Conductor Size |
Ground Check Conductor Size |
Nominal Insulation Thickness |
Nominal Sheath Thickness |
Nominal Overall Diameter |
Nominal Weight |
Ampacity |
No. of cores× AWG/kcmil |
AWG/kcmil | AWG/kcmil | mm | mm | mm | kg/km | A |
3×6 | 10 | 8 | 2.3 | 2.8 | 33 | 1577 | 93 |
3×4 | 8 | 8 | 2.3 | 2.8 | 35.8 | 2144 | 122 |
3×2 | 6 | 8 | 2.3 | 2.8 | 37.3 | 2718 | 159 |
3×1 | 5 | 8 | 2.3 | 2.8 | 39.1 | 3226 | 184 |
3×1/0 | 4 | 8 | 2.3 | 2.8 | 41.4 | 3871 | 211 |
3×2/0 | 3 | 8 | 2.3 | 2.8 | 43.7 | 4478 | 243 |
3×3/0 | 2 | 8 | 2.3 | 3.6 | 48 | 4859 | 279 |
3×4/0 | 1 | 8 | 2.3 | 3.6 | 51 | 6234 | 321 |
3×250 | 1/0 | 8 | 2.3 | 3.6 | 53.3 | 7179 | 355 |
3×350 | 2/0 | 8 | 2.3 | 3.6 | 58.7 | 9019 | 435 |
3×500 | 4/0 | 8 | 2.3 | 3.6 | 65.8 | 12538 | 536 |
Ampacity-Based on a conductor temperature of 90℃ and an ambient air temperature of 40℃, per ICEA S-75-381.
Please note that the above specifications are “general specifications” that pertain to the majority of our production. These specifications should only be used for general, informational purposes. All dimensions and specifications are nominal and are subject to normal manufacturing tolerances. All specifications are subject to change without prior notice. All pictures shown are for illustration purposes only. Actual product may vary.
Reviews
There are no reviews yet.