Products

P7/P14 BFOU 6/10Kv FR Mud Resistant Cable

Material: Cu/Mica Tape+EPR(XLPE)/SHF2/TCWB/SHF2
Voltage: 6/10KV
APPLICATION: P7 BFOU 6/10Kv Fire Resistant Cable is fire resistant, flame retardant, low smoke, halogen free and mud resistant, used for fixed installation for medium voltage power.

P7/P14 BFOU 6/10Kv Fire Resistant Mud Resistant Cable

P7/P14 BFOU 6/10Kv Fire Resistant Mud Resistant Cable Application

P7/P14 BFOU 6/10Kv Fire Resistant Mud Resistant Cable is fire resistant, flame retardant, low smoke, halogen free and mud resistant, used for fixed installation for medium voltage power.

These P7/P14 BFOU 6/10Kv cables are intended for fixed installation for power and energy transmission with a rated voltage of 6/10KV. These cables can be installed on drilling ships, drilling platforms ( jack up, semi-submersible), Production Platforms ( TLP, semi-submersible, SPAR, fixed platforms) and FPSO/FSO.

P7/P14 BFOU 6/10Kv Fire Resistant Mud Resistant Cable Standards

Design IEC60092-354
Conductor IEC60228
Insulation IEC60092-351
sheathed IEC60092-359
Flame Retardant IEC 60332-1,IEC60332-3-22
Fire Resistant IEC 60331
Smoke Density IEC61034
Mud Resistant NEK TS 606:2009

P7/P14 BFOU 6/10Kv Fire Resistant Mud Resistant Cable Construction

Classification Code Construction details
Conductor Tinned Annealed Stranded Copper Wire
Conductor Screen Semiconducting material
Insulation B Mica Tape+EP Rubber/XLPE
Insulation Screen Semiconducting material and tinned copper wire braid
Filler Water blocking fillers, if required
Bedding Halogen free compound, PETP wrapping tape will be applied over the bedding, if required
Inner Sheath F Halogen free thermosetting compound
Armor O Tinned Copper wire braided
Outer Sheath U Mud Resistant, Halogen-free Thermosetting compound SHF Mud

P7/P14 BFOU 6/10Kv Fire Resistant Mud Resistant Cable Electrical Characteristics

Nominal Cross Section Area mm² 25 35 50 70 95 120 150
Nominal Conductor Diameter mm 6.5 7.4 8.7 10.3 12.2 13.8 15.1
Maximum DC Resistant@20℃ Ω/km 0.734 0.529 0.391 0.27 0.195 0.154 0.126
Continuous Current Rating@45℃1 Core A 127 157 196 242 293 339 389
Continuous Current Rating@45℃3 Core A 89 110 137 169 205 237 272
Short Circuit Current 1s A 3580 5010 7150 10020 13590 17170 21460
Operating Voltage KV 3.6/6 3.6/6 3.6/6 3.6/6 3.6/6 3.6/6 3.6/6
Nominal Cross Section Area mm² 185 240 300 400 500 630
Nominal Conductor Diameter mm 17.0 19.6 21.9 24.5 27.5 32.3
Maximum DC Resistant@20℃ Ω/km 0.1 0.0762 0.0607 0.0475 0.0369 0.0286
Continuous Current Rating@45℃1 Core A 444 522 601 690 780 890
Continuous Current Rating@45℃3 Core A 311 365 421 483 546 623
Short Circuit Current 1s A 26470 34340 42930 57230 71540 90140
Operating Voltage KV 3.6/6 3.6/6 3.6/6 8.7/15 8.7/15 8.7/15

Note: For more than 4-cores, the current ratings may be calculated from the following formula (IN=I1/ ³√ N ), I1= Current rating for 1-core, N = Number of cores.

Ambient Temperature Correction Factors

Ambient Temperature Correction Factors 35 40 45 50 55 60 65 70 75 80
Rating Factor 1.1 1.05 1.0 0.94 0.88 0.82 0.74 0.67 0.58 0.47

P7/P14 BFOU 6/10Kv Fire Resistant Mud Resistant Cable Specification

Construction
No. of cores×Cross section
Nominal
Insulation
Thickness
Nominal
Inner Sheath
Thickness
Nominal
Outer Sheath
Thickness
Nominal
Overall
Diameter
Nominal
Weight
(mm²) mm mm mm mm kg/km
1×16 3.4 1.0 1.6 25.6 990
1×25 3.4 1.0 1.7 27.1 1150
1×35 3.4 1.0 1.7 28.5 1320
1×50 3.4 1.0 1.8 29.9 1500
1×70 3.4 1.0 1.8 31.9 1810
1×95 3.4 1.0 1.9 34.0 2160
1×120 3.4 1.2 2.0 36.1 2610
1×150 3.4 1.2 2.1 38.1 2990
1×185 3.4 1.2 2.2 39.9 3440
1×240 3.4 1.2 2.3 43.1 4180
1×300 3.4 1.2 2.4 45.9 4930
1×400 3.4 1.4 2.5 49.0 5900
1×500 3.4 1.4 2.6 52.5 7070
1×630 3.4 1.4 2.8 57.0 8690
3×16 3.4 1.4 2.4 50.2 3780
3×25 3.4 1.4 2.6 53.2 4380
3×35 3.4 1.4 2.7 56.4 5040
3×50 3.4 1.4 2.8 59.3 5740
3×70 3.4 1.6 2.9 63.7 6900
3×95 3.4 1.6 3.1 68.4 8270
3×120 3.4 1.6 3.2 72.1 9470
3×150 3.4 1.6 3.4 76.0 10800
3×185 3.4 1.8 3.5 80.8 12370
3×240 3.4 1.8 3.8 88.2 15040
3×300 3.4 2.0 3.9 94.0 17450

Please note that the above specifications are “general specifications” that pertain to the majority of our production. These specifications should only be used for general, informational purposes. All dimensions and specifications are nominal and are subject to normal manufacturing tolerances. All specifications are subject to change without prior notice. All pictures shown are for illustration purposes only. Actual product may vary. Classification certification like CCS, DNV, BV, LR, NK, KR, RS shall be provided upon request.

Reviews

There are no reviews yet.

Be the first to review “P7/P14 BFOU 6/10Kv FR Mud Resistant Cable”

Your email address will not be published. Required fields are marked *

This site uses Akismet to reduce spam. Learn how your comment data is processed.